Electrical installation

Drive system on the mains

Supply forms / electrical supply conditions

4

80

EDKCSEE040 DE/EN/FR 4.0

4.2.2

Supply forms / electrical supply conditions

Stop!

The power supply module may only be operated on balanced mains

supplies. Operation on mains supplies with earthed phase is not

permitted.

The ECSxE series power supply modules are provided with an automatic

detection of the mains voltage and adapt the brake chopper switch-on voltage.
Please observe the restrictions for the respective supply forms:

Mains

Operation of the power supply

modules

Notes

With earthed

neutral (TT/TN

systems)

No restrictions

Observe the rated data of the power

supply modules.

With isolated

neutral (IT

systems)

The ECSxExxxx4I IT variant can be

used if the power supply module is

protected in the event of an earth

fault in the mains supply:

by suitable equipment detecting

the earth fault.

by disconnecting the power supply

module immediately from the

mains.

In the event of an earth fault at the

output of the power supply module,

safe operation cannot be guaranteed.

Note!

ƒ

Mains voltage dips can be reduced by decreasing the max.

charging current limit (C0022).

ƒ

Deactivate the charging current limitation (charge relay) of the

connected ECS axis modules with C0175 = 3.