Electrical installation – Lenze ECSEExxx User Manual
Page 105
![background image](/manuals/566127/105/background.png)
Electrical installation
Wiring of system bus (CAN)
4
105
EDKCSEE040 DE/EN/FR 4.0
Example: Selection help
Specifications
Cable cross-section:
0.5 mm
2
(according to cable specifications
103)
Number of nodes:
63
Repeater:
Lenze-repeater, type EMF2176IB (cable reduction: 30 m)
For the max. number of nodes (63), the following cable lengths / number of
repeaters from the specifications must be observed:
Baud rate [kbit/s]
50
120
250
500
1000
Max. cable length [m]
1500
630
290
120
25
Segment cable length [m]
310
310
290
120
25
Number of repeaters
5
2
-
-
-
Check repeater application
Given:
Baud rate:
125 kbps
Cable cross-section:
0.5 mm
2
Number of nodes:
28
Cable length:
450 m
Procedure
Cable length
See
1. Total cable length at 125 kbps:
630 m
Tab. 4-1
2. Segment cable length for 28 bus nodes and a cable
cross-section of 0.5 mm
2
:
360 m
Tab. 4-2
3. Comparison: The value under point 2 is smaller than the required cable length of 450 m.
Conclusion
It is not possible to use a cable length of 450 m without using a repeater.
After 360 m (point 2) a repeater must be installed.