Electrical installation – Lenze ECSEExxx User Manual

Page 77

Advertising
background image

Electrical installation

Installation according to EMC (installation of a CE-typical drive system)

4

77

EDKCSEE040 DE/EN/FR 4.0

Assembly

ƒ

Connect the ECS modules, RFI filters, and mains choke to the earthed

mounting plate with a surface as large as possible:

Mounting plates with conductive surfaces (zinc-coated or stainless

steel) allow for permanent contact.

Painted plates are not suitable for an EMC-compliant installation.

ƒ

If you use the ECSxK... capacitor module:

Install the capacitor module between the power supply module and the

axis module(s).

If the total cable length in the DC-bus connection is > 5 m, install the

capacitor module as close as possible to the axis module with the

greatest power.

ƒ

If you use several mounting plates:

Connect as much surface of the mounting plates as possible (e.g. with

copper bands).

ƒ

Ensure the separation of the motor cable and the signal or mains cables.

ƒ

Avoid a common terminal/power strip for the mains input and motor

output.

ƒ

Lay the cables as close as possible to the reference potential. Freely

suspended cables act like aerials.

Filters
Only use RFI filters and mains chokes which are assigned to the power supply

modules:

ƒ

RFI filters reduce impermissible high-frequency interferences to a

permissible value.

ƒ

Mains chokes reduce low-frequency interferences which in particular

depend on the motor cables and their lengths.