background image

Electrical installation

Power terminals

Connection to the DC bus (+U

G

, -U

G

)

4

88

EDKCSEE040 DE/EN/FR 4.0

Fuses
Fusing the DC-bus interconnection is not required if power supply modules of

the ECS series are used which are fused on the mains side.
Cable cross-section

Cable

length

(module/

module)

Wire end ferrule

Cable

cross-section

Tightening torque

Stripping length

Up to 20 m

Without wire end

ferrule

6 mm

2

(AWG 10)

1.2 ... 1.5 Nm

(10.6 ... 13.3 lb-in)

5 mm for screw

connection

10 mm for spring

connection

With insulated wire

end ferrule

> 20 m

Without wire end

ferrule

10 mm

2

(AWG 8)

With insulated wire

end ferrule

Use pin-end

connectors for

wiring!