3 mechanical installation, Important notes, Mechanical installation – Lenze ECSEExxx User Manual

Page 73

Advertising
background image

Mechanical installation

Important notes

3

73

EDKCSEE040 DE/EN/FR 4.0

3

Mechanical installation

3.1

Important notes

ƒ

ECS power supply modules are provided with IP20 enclosure and can

therefore only be used for installation in control cabinets.

ƒ

If the cooling air contains air pollutants (dust, fluff, grease, aggressive

gases):

Take suitable preventive measures , e.g. separate air duct, installation

of filters, regular cleaning.

ƒ

Possible mounting positions

Vertical at the mounting plate

DC bus connections (X22) at the top

Mains connection (X21) at the bottom

ƒ

Maintain the specified clearances (above and below) to other

installations!

If the ECSZS000X0B shield mounting kit is used, an additional clearance

is required.

Ensure unimpeded ventilation of cooling air and outlet of exhaust air.

Several modules of the ECS series can be installed in the control cabinet

next to each other without any clearance.

ƒ

The mounting plate of the control cabinet

must be electrically conductive.

must not be varnished.

ƒ

In case of continuous vibrations or shocks use shock absorbers.