Electrical installation

Power terminals

Connection plan for mimimum wiring with external brake resistor

4

91

EDKCSEE040 DE/EN/FR 4.0

4.3.4

Connection plan for mimimum wiring with external brake resistor

Stop!

ƒ

Always operate the ECS power supply modules with a brake

resistor.

ƒ

A parallel wiring of internal and external brake resistor is not

permissible!

ƒ

Implement the thermal contact of the brake resistor into the

system monitoring so that the mains supply of the power supply

module will be switched off in case the brake resistor will be

overheated.

ƒ

Read the documentation for the external brake resistor. Observe

the safety instructions contained therein.

If the power supply module needs a high amount of braking power when it

comes as standard built-in unit or in push-through technique design (ECSEE /

ECSDE), an external and more powerful brake resistor can be connected instead

of the internal brake resistor.
A power supply module in cold plate technique design (ECSCE) is not provided

with an internal brake resistor so that this version always requires an external

brake resistor (Rbext).

ƒ

Connect the brake resistor to X22/BR1 and X22/+UG.

ƒ

Connect the thermal contact (NC contact) of the external brake resistor to

X6/T1 and X6/T2.