Safety instructions, Warnings – Lenze ECSEExxx User Manual

Page 65

Advertising
background image

Safety instructions

Safety instructions for the installation according to UL

1

65

EDKCSEE040 DE/EN/FR 4.0

1.3

Safety instructions for the installation according to UL

Warnings!

General markings:

ƒ

Use 60/75 °C or 75 °C copper wire only.

ƒ

Maximum ambient temperature 55 °C, with reduced output

current.

Markings provided for the supply units:

ƒ

Suitable for use on a circuit capable of delivering not more than

5000 rms symmetrical amperes, 480 V max, when protected by

K5 or H Fuses (400/480 V devices).

ƒ

Alternate - Circuit breakers (either inverse-time, instantaneous

trip types or combination motor controller type E) may be used in

lieu of above fuses when it is shown that the let-through

energy (i

2

t) and peak let-through current (I

p

) of the inverse-time

current-limiting circuit breaker will be less than that of the

non-semiconductor type K5 fuses with which the drive has been

tested.

ƒ

Alternate - An inverse-time circuit breaker may be used, sized

upon the input rating of the drive, multiplied by 300 %.

Markings provided for the inverter units:

ƒ

The inverter units shall be used with supply units which are

provided with overvoltage devices or systems in accordance with

UL840 2nd ed., Table 5.1.

ƒ

The devices are provided with integral overload and integral

thermal protection for the motor.

ƒ

The devices are not provided with overspeed protection.

Terminal tightening torque of lb-in (Nm)

Terminal

lb-in

Nm

X 21, X 22, X 23, X 24

10.6 ... 13.3

1.2 ... 1.5

X4, X6, X14

1.95 ... 2.2

0.22 ... 0.25

X 25

4.4 ... 7.1

0.5 ... 0.8

Wiring diagram AWG

Terminal

AWG

X 21, X 22, X 23, X 24

12 ... 8

X4, X6, X14

28 ... 16

X 25

24 ... 12