Electrical installation

Installation according to EMC (installation of a CE-typical drive system)

4

78

EDKCSEE040 DE/EN/FR 4.0

Shielding

ƒ

Connect the motor cable shield to the axis module

with the ECSZS000X0B shield mounting kit.

extensively to the mounting plate below the axis module.

Recommendation: For the shield connection, use earthing clamps on

bare metal mounting surfaces.

ƒ

If contactors, motor protection switches or terminals are located in the

motor cable:

Connect the shields of the connected cables to each other and connect

them to the mounting plate, too, with a surface as large as possible.

ƒ

Connect the shield in the motor terminal box or on the motor housing

extensively to PE:

Metal glands at the motor terminal box ensure an extensive connection

of the shield and the motor housing.

ƒ

Shield UG cables and control cables from a length of 0.3 m:

Connect both shields of the digital control cables.

Connect one shield end of the analog control cables.

Always connect the shields to the shield connection at the axis module

over the shortest possible distance.

ƒ

Use of the ECS modules in residential areas:

Additionally dampen the shield in order to limit the interfering

radiation: 10 dB . This can be achieved by using standard, closed,

metallic, and earthed control cabinets or boxes.

Earthing

ƒ

Earth all metallically conductive components (e.g. ECS modules, RFI filters,

motor filters, mains chokes) using suitable cables connected to a central

earthing point (PE rail).

ƒ

Maintain the minimum cross-sections prescribed in the safety

regulations:

For EMC not the cable cross-section is important, but the surface of the

cable and the contact with a cross-section as large as possible, i.e. large

surface.