Lenze ECSEExxx User Manual

Page 89

Advertising
background image

Electrical installation

Power terminals

Connection plan for mimimum wiring with internal brake resistor

4

89

EDKCSEE040 DE/EN/FR 4.0

4.3.3

Connection plan for mimimum wiring with internal brake resistor

Stop!

Always operate the ECS power supply modules with a brake resistor

(internal/external).

The ECS power supply modules in the standard built-in unit and push-through

design (ECSEE / ECSDE) are provided with a device-internal brake resistor.
In order to use the internal brake resistor (Rb), carry out the following wiring:

ƒ

Bridge between the terminals X22/+UG and X22/BR0 (CR)

Current flow from +UG via the internal brake resistor (Rb) and the brake

transistor to -UG.

ƒ

Bridge between the terminals X6/T1 and X6/T2 (CR)

Deactivate the temperature monitoring of the non-existing external brake

resistor.

Advertising