Electrical installation

Power terminals

Connection to the DC bus (+U

G

, -U

G

)

4

87

EDKCSEE040 DE/EN/FR 4.0

4.3.2

Connection to the DC bus (+U

G

, -U

G

)

Stop!

ƒ

The supply of Lenze controllers of the 82xx and 93xx series is not

permitted.

ƒ

If synchronous motors with a high centrifugal mass are used, a

considerable amount of energy can be fed back into the DC bus.

Please take this into account when dimensioning the brake

resistor.

ƒ

If the total cable length is > 20 m, install an axis module or a capacitor

module directly at the power supply module.

ƒ

Design the ±U

G

cables twisted and as short as possible. Ensure

short-circuit-proof routing!

ƒ

Cable length (module  module) > 30 cm: install shielded ±U

G

cables.

Documentation of the ECSxS/P/M/A axis modules
Observe the enclosed notes.

Documentation of the ECSxK capacitor module
Observe the enclosed notes.