Technical data

General data and operating conditions

2

69

EDKCSEE040 DE/EN/FR 4.0

General electrical data
EMC

Compliance with the requirements acc. to EN 61800-3

Noise emission

Compliance with the limit class C2 according to EN 61800-3(achieved

with a collective filter typical for the application)

Noise immunity

Requirements acc. to EN 61800-3
Requirement

Standard

Severity

ESD

1)

EN 61000-4-2

3, i. e.

8 kV for air discharge

6 kV for contact

discharge

Conducted high

frequency

EN 61000-4-6

10 V; 0.15 ... 80 MHz

RF interference

(housing)

EN 61000-4-3

3, i. e. 10 V/m;

80 ... 1000 MHz

Burst

EN 61000-4-4

3/4, i. e. 2 kV/5 kHz

Surge (surge voltage on

mains cable)

EN 61000-4-5

3, i. e. 1.2/50 s

1 kV phase/phase

2 kV phase/PE

Insulation resistance

EN 61800-5-1, UL 840: Overvoltage category III

Discharge current to PE

(Acc. to EN 61800-5-1)

> 3.5 mA AC

Enclosure

IP20 for

Standard installation (built-in unit)

Cold-plate technique

Mounting with thermal separation (push-through technique), IP54

on heatsink side

Protective measures against

Short circuit in power terminals (short-circuit-proof at mains

connection)

Short circuit in auxiliary circuits

– Digital outputs: Short-circuit-proof

– Bus and encoder systems: Limited protection against short circuit

(if necessary, monitoring functions can be switched off, in this

case, error messages must be reset:)

Earth fault (earth-fault protected at mains connection)

Overvoltage

Protective insulation of control circuits Protective separation from the mains

Double/reinforced insulation acc. to EN 61800-5-1

1)

The noise immunity with the severities given must be ensured by the control cabinet.

The user must check the compliance of the severities given.