05

.

06

Han

Com

Han

®

K 4/4

Features

• Combination of power area and signal area in the

same connector

• Axial screw termination for power area

• Cage clamp termination for signal area

• Finger safe

• Same range of wire gauge for PE contact and

power contacts

Assembly instructions see page 05.22

Current carrying capacity

The current carrying capacity of the connectors is limited by the

thermal load capability of the contact element material including

the connections and the insulating parts. The derating curve

is therefore valid for currents which flow constantly (non-inter-

mittent) through each contact element of the connector evenly,

without exceeding the allowed maximum temperature.

Measuring and testing techniques according to

DIN EN 60 512-5-2

Operating current

Ambient temperature

Wire gauge:

➀ 16 mm²
➁ 22 mm²

Technical characteristics

Specifications

DIN EN 60 664-1

DIN EN 61 984

Approvals

Inserts

Number of contacts

4 / 4 + PE

Electrical data

acc. to EN 61 984

Power area

63 A 690 V 8 kV 3

Rated current

63 A

Rated voltage

690 V

Rated impulse voltage

8 kV

Pollution degree

3

Signal area

16 A 250 V 4 kV 3

Rated current

16 A

Rated voltage

250 V

Rated impulse voltage

4 kV

Pollution degree

3

Rated voltage

acc. to UL

600 V / 230 V

Insulation resistance

≥ 10

10

Ω

Material polycarbonate

Limiting temperatures

-40 °C ... +125 °C

Flammability acc. to UL 94

V 0

Mechanical working life

- mating cycles

≥ 500

Contacts

Power contacts

Material

copper alloy

Surface

- hard-silver plated

3 µm Ag

Contact resistance

≤ 0.5 mΩ

Axial screw termination

- geometric wire gauge

6 ... 22 mm²

- AWG

8 ... 4

Max. insulation diameter

6 ... 16 mm²

8.9 mm

22 mm²

11 mm

Tightening tourque

mm² 6 10 16 22

Nm 2

3

4

4

Stripping length

mm² 6 10 16 22

mm 11

+1

11

+1

11

+1

13

+1

Signal contacts

Material

copper alloy

Surface

- hard-silver plated

3 µm Ag

Contact resistance

≤ 3 mΩ

Cage clamp terminal

- geometric wire gauge

0.14 ... 2.5 mm²

- AWG

26 ... 14

Stripping length

7 ... 9 mm

Hoods/Housings

see chapter 31

Advertising