Han

00

.

19

Terminations technology

Insert

Wire

gauge

Stripping length

Tightening

torque

Max. cable

insulation

diameter

Size

hexagon

recess

Insert dimension

for cable

indication (ISK)

(mm²)

(mm)

(Nm)

(mm)

(SW)

(mm)

Han

®

C module with axial screw

terminal

2.5 ... 8

2.5 mm²:

4 mm²:
6 mm²:
8 mm²:

5+1
5+1
8+1
8+1

2.5 mm²:

4 mm²:
6 mm²:
8 mm²:

1.5
1.5

2
2

4
4
6

8.2

2

5.2

6 ... 10

6 mm²:

10 mm²:

8+1

11+1

6 mm²:

10 mm²:

2
2

6

8.2

2

5.2

Han

®

K3/0 straight

25 ... 40

25 mm²:
40 mm²:

22
22

25 mm²:
40 mm²:

8
8

15

5

8.2

35 ... 70

35 mm²:
50 mm²:
70 mm²:

22
22
22

35 mm²:
50 mm²:
70 mm²:

8
9

10

15

5

8.2

Han

®

K3/0 angled

25 ... 40

25 mm²:
40 mm²:

22
22

25 mm²:
40 mm²:

8
8

15

5

9

35 ... 70

35 mm²:
50 mm²:
70 mm²:

22
22
22

35 mm²:
50 mm²:
70 mm²:

8
9

10

15

5

9

Han

®

K3/2 straight

35 ... 70

PE: 25 ... 40

35 mm²:
50 mm²:
70 mm²:

PE:

22
22
22
14

35 mm²:
50 mm²:
70 mm²:

8
9

10

power: 15


PE: 10

5

power: 8.2


PE: 7.2

Han

®

K3/2 angled

25 ... 40

25 mm²:
40 mm²:

PE:

22
22
14

25 mm²:
40 mm²:

8
8

power: 15

PE: 10

5

power: 9.0

PE: 7.2

35 ... 70

PE: 25 ... 40

35 mm²:
50 mm²:
70 mm²:

22
22
22

35 mm²:
50 mm²:
70 mm²:

8
9

10

power: 15

PE: 10

5

power: 9.0

PE: 7.2

Han

®

HC Modular 350

20 ... 35

20 mm²:
35 mm²:

19+1
19+1

20 mm²:
35 mm²:

8
8

19.5

5

13

35 ... 70

35 mm²:
50 mm²:
70 mm²:

19+1
19+1

19+1

35 mm²:
50 mm²:
70 mm²:

8

10
12

19.5

5

13

95 ... 120

95 mm²:

120 mm²:

19+1
19+1

95 mm²:

120 mm²:

14
16

19.5

5

13

Ground contact for
Han

®

HC Modular

35 ... 70

35 mm²:
50 mm²:
70 mm²:

19+1
19+1
19+1

35 mm²:
50 mm²:
70 mm²:

8

10
12

-

5

-

Han

®

HC Modular 650

60 ... 70

60 mm²:
70 mm²:

23+2
23+2

60 mm²:
70 mm²:

12
12

27

8

28

70 ... 120

70 mm²:
95 mm²:

120 mm²:

23+2
23+2
23+2

70 mm²:
95 mm²:

120 mm²:

12
14
16

26.5

8

28

150 ... 185

150 mm²:
185 mm²:

23+2
23+2

150 mm²:
185 mm²:

17
18

26.5

8

28

Overview inserts with axial screw terminal

Insulating base dimension for the cable marking (ISK)

Marking the proper cable position for the axial screw connection contact point:

The user can attach a marker to the cable sheathing in order to specify the proper point for tightening the axial screw on the connecting

cable. If the cable in pushed into the insulating base up to the marker (where the marker is flush with the upper edge of the insulating

base), then the cable is in the proper position and may be connected. The following figure (on the next page) illustrates this process

when using the Han

®

HC Modular 350 contact. The marker and the upper edge of the insulating base are at the same level (as indicated

by the dashed line).