15

.

12

Power

Distribution

Han-Power

®

S with 1x Han

®

Q 8/0

Features

• 6 IDCs + PE for 2.5 mm² up to 6 mm² wire gauge

• No interuption of the energy supply

• Space-saving and compact design

• Leading protective ground within the insert

• Assembly with standard tools

Description

The Han-Power

®

S connector is suitable for the assembly of

serial power bus. Having assembled the energy supply Han-

Power

®

S can be inserted at any place of the power cable.

The cable jacket has to be removed, the conductor is placed

without interruption in the IDC.

Han-Power

®

S is suitable for cables with single strands manuf-

actured acc. to DIN VDE 0281/ DIN EN 60 228 with wire gau-

ges of 2.5 mm² up to 6 mm². For the distribution of the device

Han-Compact

®

hoods or cable to cable housings are used.

This power supply has to be realized with one Han-Compact

®

cable to cable hood.

Current carrying capacity

The current carrying capacity of the connectors is limited by the

thermal load capability of the contact element material including

the connections and the insulating parts. The derating curve

is therefore valid for currents which flow constantly (non-inter-

mittent) through each contact element of the connector evenly,

without exceeding the allowed maximum temperature.

Measuring and testing techniques according to

DIN EN 60 512-5-2

Operating

current

Ambient temperature

➀ Han

®

Q 8/0 Wire gauge: 2.5 mm²

➁ Han

®

Q 8/0 Wire gauge: 4 mm²

➁ Han

®

Q 8/0 Wire gauge: 6 mm²

Han

®

Q 8/0 partly loaded

with wire gauge 7x 4 mm²

Technical characteristics

Specifications

DIN EN 61 984

DIN EN 60 664-1

Han-Power

®

S

Number of contacts

- Power contacts

6 + PE

Electrical data

acc. to EN 61 984

25 A 500 V 6 kV 3

Rated current

25 A

Rated voltage

500 V

Rated impulse voltage

6 kV

Pollution degree

3

Rated voltage

acc. to UL/CSA

600 V

Insulation resistance

≥ 10

10

Material

polycarbonate

Limiting temperatures

-40 °C ... +125 °C

Flammability acc. to UL 94

V 0

Mechanical working life

- mating cycles

≥ 500

Degree of protection acc. to DIN EN 60 529 IP 65

Contacts

Material

copper alloy

Surface

- hard-silver plated

3 µm Ag

Contact resistance

≤ 1 mΩ

Crimp terminal

- mm²

2.5 ... 6 mm²

- AWG

14 ... 10

Cables

Design of conductor acc. to

DIN VDE 0281

DIN EN 60 228

Single strand

Wire gauge

2.5 mm²

- Number of single strands

50 x 0.25 mm ∅

- Outer diameter

3.6 mm

Wire gauge

4 mm²

- Number of single strands

56 x 0.3 mm ∅

- Outer diameter

4.2 mm

Wire gauge

6 mm²

- Number of single strands

84 x 0.3 mm ∅

- Outer diameter

4.8 mm