00 . 14 terminations technology, Screw terminal – Northern Connectors Harting HAN Industrial Rectangular Connectors User Manual

Page 20

Advertising
background image

Han

00

.

14

Terminations technology

Screw terminal


Screw terminals meet VDE 0609 /EN 60 999. Dimensions and
tightening torques for testing are shown in following table.
Screw dimensions and tightening torque for screw terminals

Wire gauge (mm²)

1.5

2.5

4

6

10

16

Screw thread

M3

M3

M3.5

M4

M4

M6

Test moment of torque
(Nm)

0.5

0.5

0.8

1.2

1.2

1.2*

min. pull-out for stranded
wire (N)

40

50

60

80

90

100

* for screws without heads

The relevant regulations state that in the case of

● Terminals with wire protection

the use of ferrules is not necessary. Series Han E

®

,

Han

®

HsB, Han Hv E

®

, Han

®

K 6/12, Han

®

K 6/6

● Terminals without wire protection

The insulation is first stripped and then a wire ferrule must be

used.
Series Han

®

K 4/x, Han A

®

, Staf

®

Screw terminal

Inserts

Wire protection

min. wire gauge

max. wire gauge*

Stripping length

Yes

No

mm²

AWG

mm²

AWG

mm

Han

®

3 A, Han

®

4 A

X

0.75

18

1.5

16

4.5

Han

®

10 A, 16 A, 32 A

X

0.75

18

2.5

14

7.5

Han E

®

, Hv E

®

X

0.75

18

2.5

14

7.5

Han

®

HsB

X

1.5

16

6

10

11.5

Han

®

K 6/6, K 6/12

(signal contacts)

X

0.2

24

2.5

14

7.5

Han

®

K 4/2, K 4/8

(signal contacts)

X

0.5

20

2.5

14

7.5

Han

®

K 4/0, K 4/2, K 4/8

(power contacts)

X

1.5

16

16

6

14

Han E

®

AV, Han D

®

AV

X

0.2

24

2.5

14

8 ... 11

Staf

®

X

0.5

18

1.5

16

4.5

* Rated wire gauge according to DIN EN 60 999-1