Han-power, S with 1x han, Q 4/2 with power supply 24 v – Northern Connectors Harting HAN Industrial Rectangular Connectors User Manual

Page 271: Features technical characteristics han-power, Assembly details, Current carrying capacity base element

Advertising
background image

15

.

06

Power

Distribution

Features

Technical characteristics

Han-Power

®

S with 1x Han

®

Q 4/2 with Power Supply 24 V

• 6 IDC‘s + PE for 4.0 mm² to 6.0 mm² wires
• No interruption of the energy supply
• Space-saving and compact design
• Leading protective ground within the insert
• Assembly with standard tools

24 V power supply integrated

Secondary connection 2 x M12

Assembly Details

Specifications

DIN EN 61 984

DIN EN 60 664-1

Han-Power

®

S

Number of contacts

- Power contacts

4 + PE

- Signal contacts 2

Electrical data

acc. to EN 61 984

Power side

40 A 230/400 V 4 kV 2

Rated current

40 A

Rated voltage conductor - ground

230 V

Rated voltage conductor - conductor 400 V

Rated impulse voltage

4 kV

Pollution degree

2

Signal side

10 A 250 V 4 kV 2

Rated current

10 A

Rated voltage

250 V

Rated impulse voltage

4 kV

Pollution degree

2

Rated voltage

acc. to UL/CSA

600 / 250 V

Insulation resistance

≥ 10

10

Material

polycarbonate

Limiting temperatures

- without derating

-20 °C ... +50 °C

- with derating

-20 °C ... +70 °C

Flammability acc. to UL 94

V 0

Mechanical working life

- mating cycles

≥ 500

Degree of protection acc. to DIN EN 60 529 IP 65

Cables

Design of conductor acc. to

DIN VDE 0281

DIN EN 60 228

Wire gauge

4 mm²

- Number of single strands

56 x 0.3 mm ∅

- Outer diameter

4.2 mm

Wire gauge

6 mm²

- Number of single strands

84 x 0.3 mm ∅

- Outer diameter

4.8 mm

Technical data power supply

Input data

100 V ... 240 V AC

(50 Hz / 60 Hz)

Output data

24 V DC / 2 A

(adjustable from 23 V ... 29 V)

Pre-setting: 24.5 V ± 0,5 %

Efficiency

>86% (at 230 V AC)

Reverse voltage

max 32 V

Tide overtime for power-fail

>20 ms

Low voltage system

SELV / PELV

Additionally features

short-circuit proof

open-circuit proof

automatic switch off in

the case of short-circuit

Green LED marks normal operating condition.

Han

®

Q 4/2 fully loaded

with wire gauge 4 x 6 mm²

➀ Han

®

Q 4/2 Wire gauge: 4 mm²

➁ Han

®

Q 4/2 Wire gauge: 6 mm²

Ambient temperature

Operating

current

The current carrying capacity of the connectors is limited by the

thermal load capability of the contact element material including

the connections and the insulating parts. The derating curve

is therefore valid for currents which flow constantly (non-inter-

mittent) through each contact element of the connector evenly,

without exceeding the allowed maximum temperature.

Measuring and testing techniques according to DIN EN 60 512-

5-2

The Han-Power

®

S connector is suitable for the assembly of

serial power bus. Having assembled the energy supply

Han-Power

®

S can be inserted at any place of the power cable.

The cable jacket has to be removed, the conductor is placed

without interruption in the IDC.

Han-Power

®

S is suitable for cables with single strands

manufactured acc. to DIN VDE 0281/ DIN EN 60 228 with wire

gauges of 4.0 mm² up to 6 mm². For the distribution of the

device Han-Compact

®

hoods or cable to cable housings are

used. This power supply can be used with Han-Compact

®

hood.