Han® k 4/8, K 4/8, K 4/8 features – Northern Connectors Harting HAN Industrial Rectangular Connectors User Manual

Page 128: Technical characteristics

Advertising
background image

05

.

16

Han

Com

Han

®

K 4/8

Features

• Combination of power and signal area in one

connector

• Screw termination for power and signal area

In accordance with the appropriate regulations a wire-end

sleeve has to be used at clamps without wire protection

(see „Screw terminal“, chapter 00).

Current carrying capacity

The current carrying capacity of the connectors is limited by the

thermal load capability of the contact element material including

the connections and the insulating parts. The derating curve

is therefore valid for currents which flow constantly (non-inter-

mittent) through each contact element of the connector evenly,

without exceeding the allowed maximum temperature.

Measuring and testing techniques according to

DIN EN 60 512-5-2

Operating current

Ambient temperature

Wire gauge:

➀ 16 mm²
➁ 10 mm²

Technical characteristics

Specifications

DIN EN 60 664-1

DIN EN 61 984

Approvals

,

,

Inserts

Number of contacts

4 / 8 + PE

Electrical data

acc. to EN 61 984

Power area

80 A 400 V 6 kV 3

Rated current

80 A

Rated voltage

400 V

Rated impulse voltage

6 kV

Pollution degree

3

Pollution degree 2 also

80 A 400/690 V 6 kV 2

Signal area

16 A 400 V 6 kV 3

Rated current

16 A

Rated voltage

400 V

Rated impulse voltage

6 kV

Pollution degree

3

Rated voltage

acc. to UL/CSA

600 V / 600 V

Insulation resistance

≥ 10

10

Ω

Material Polyamide

Limiting temperatures

-40 °C ... +125 °C

Flammability acc. to UL 94

HB

Mechanical working life

- mating cycles

≥ 500

Contacts

Power contacts

Material

copper alloy

Surface

- hard-silver plated

3 µm Ag

Contact resistance

≤ 0.3 mΩ

Screw terminal

- geometric wire gauge

1.5 ... 16 mm²

- AWG

16 ... 6

Tightening tourque

mm² 1.5 2.5 4 6 10 16

Nm 1.2 2 3 3 3 3

Stripping length

14 mm

Signal contacts

Material

copper alloy

Surface

- hard-silver plated

3 µm Ag

Contact resistance

≤ 1 mΩ

Screw terminal

- geometric wire gauge

0.5 ... 2.5 mm²

- AWG

20 ... 14

Tightening tourque

0.5 Nm

Stripping length

7.5 mm

Hoods/Housings

see chapter 31

Advertising