Han-power® t with 3x han® q 2/0, Han-power, T with 3x han – Northern Connectors Harting HAN Industrial Rectangular Connectors User Manual

Page 287: Q 2/0, Q 2/0 features, Technical characteristics

Advertising
background image

15

.

22

Power

Distribution

Han-Power

®

T with 3x Han

®

Q 2/0

Features

• Per 1 connection for power input, power output

and to device

• 2 power contacts

• Plastic housings are integrated in the moulding

• Compact design

Current carrying capacity

The current carrying capacity of the connectors is limited by the

thermal load capability of the contact element material including

the connections and the insulating parts. The derating curve

is therefore valid for currents which flow constantly (non-inter-

mittent) through each contact element of the connector evenly,

without exceeding the allowed maximum temperature.

Measuring and testing techniques according to

DIN EN 60 512-5-2

Operating

current

Ambient temperature

Wire gauge:

6 mm²

Technical characteristics

Specifications

DIN EN 61 984

DIN EN 60 664-1

Han-Power

®

T

Number of contacts

- Power contacts

2 + PE

Electrical data

acc. to EN 61 984

Power side

40 A 400 V 6 kV 3

Rated current

40 A

Rated voltage

400 V

Rated impulse voltage

6 kV

Pollution degree

3

Rated voltage

acc. to UL/CSA

600 V

Insulation resistance

≥ 10

10

Ω

Material

polycarbonate

Limiting temperatures

-40 °C ... +125 °C

Flammability acc. to UL 94

V 0

Mechanical working life

- mating cycles

≥ 500

Degree of protection acc. to DIN EN 60 529 IP 65 / IP 67

Contacts

Material

copper alloy

Surface

- hard-silver plated

3 µm Ag

Contact resistance

≤ 1 mΩ

Crimp terminal

- mm²

2.5 ... 10 mm²

- AWG

14 ... 8