32 • Setup Mode

Diffusion Eagle Instruction Manual

Returning to the main menu

1. Press the SHIFT/

button. The ESCAPE message displays. (Press the

AIR/

button to return to the previous screen.)

2. Press the POWER/ENTER button to save the new setting. The OTHER

GAS SET message displays, then the Gas Combinations menu displays.

3. To exit the Gas Combinations menu, press the SHIFT/

button until the

prompt is next to Channel 4, then press SHIFT/

again. The ESCAPE

message displays.

4. Press the POWER/ENTER button. The message SAVING DATA

displays, then the main menu displays.

Updating oxygen channel settings

This section describes how to update the target gas label, full-scale setting,
and display increment setting for the oxygen channel.

Updating the target gas label

1. From the main menu, select the GAS COMBINATIONS menu option.

2. Use the AIR/

or SHIFT/

button to place the prompt next to the oxygen

channel (in this example OXY).

3. Press the POWER/ENTER button. The oxygen target gas label flashes.

This indicates that this setting can now be updated.

4. Press the AIR/

or SHIFT/

buttons to display the available oxygen

target gas labels (OXY, ***, and NOT USED).

CAUTION:

The *** setting is not intended for customer setup.
Contact RKI Instruments, Inc., before using this setting
for the oxygen channel.

5. Press the POWER/ENTER button to enter the new target gas label.

6. To exit the Gas Combinations menu, press the SHIFT/

button until the

prompt is next to Channel 4, then press the SHIFT/

button again. The

ESCAPE message displays.

7. Press the POWER/ENTER button. The SAVING DATA message

displays, then the main menu displays.