Updating Combustible Gas Channel Units of Measure

This setting allows you to display the combustible gas reading in percentage
of LEL or percentage of volume. The detection range remains the same. If
100% LEL equals 5% by volume, then full-scale on the volumetric display is
5%.

1. From the main menu, select the LEL% OR VOL% (HC) menu option.

2. Press the AIR/

or SHIFT/

button to display the desired setting.

NOTE: The data logging option logs all combustible gas readings in LEL%

regardless of this setting.

3. Press the POWER/ENTER button to enter the setting and return to the

main menu.

Updating the Alarm Point Settings

Each of the Eagle’s gas detection channels includes low and high gas alarms.
The combustible gas channel also includes low and high alarms for PPM
readings; the toxic gas channels also include STEL and TWA alarms.

This screen allows you to update one or more alarm points (the reading at
which the Eagle recognizes the alarm).

1. From the main menu, select the ALARM POINTS menu option.

2. Select the channel of the alarm point you want to update. The channel’s

Set Low Alarm Point screen displays (in this example for the combustible
gas channel).

NOTE: The Eagle displays the set alarm point screens for each channel in

the following sequence: low alarm, high alarm, TWA alarm (toxics
only), and STEL alarm (toxics only).

%