4 • Specifications
Diffusion Eagle Instruction Manual
Table 2 lists specifications for the Eagle’s standard sensors. Your Eagle model
may not include all of the sensors listed below. The alarm settings are user-
adjustable (see “Updating the Alarm Point Settings” on page 36.)
Table 2: Standard Sensor Specifications
Combustible
Gas (%LEL
1
)
Combustible
Gas (PPM
2
)
Oxygen
Hydrogen
Sulfide
Carbon
Monoxide
Range
0 to 100% LEL
Depends on
target gas
4
0 to 40% O
2
0 to 100 ppm
0 to 500 ppm
Alarm 1
10% LEL
5000 ppm
19.5% O
2
(decreasing)
10.0 ppm
25 ppm
Alarm 2
50% LEL
25,000 ppm
23.5% O
2
(increasing)
30.0 ppm
50 ppm
TWA Alarm
N/A
N/A
N/A
10.0 ppm
25 ppm
STEL Alarm
N/A
N/A
N/A
15.0 ppm
400 ppm
Detection
Principle
Catalytic
combustion
Catalytic
combustion
Electro-
chemical
Electro-
chemical
Electro-
chemical
Response Time
(to 90%)
15 seconds
15 seconds
20 seconds
40 seconds
55 seconds
Accuracy
(of full-scale)
± 5%
± 5%
± 5%
± 5%
± 5%
1 LEL (Lower Explosive Limit)
2 PPM (Parts Per Million)
3 Alarms settings are user adjustable. See “Updating the Alarm Point Settings” on page 36.
4 The PPM range represents the same range as 0 to 100% LEL for that gas. For example, 100% LEL for methane = 5% by
volume = 50,000 PPM. Therefore, the PPM range for methane is 0 to 50,000.