RKI Instruments Eagle Series User Manual

Page 9

Advertising
background image

4 • Specifications

Diffusion Eagle Instruction Manual

Table 2 lists specifications for the Eagle’s standard sensors. Your Eagle model
may not include all of the sensors listed below. The alarm settings are user-
adjustable (see “Updating the Alarm Point Settings” on page 36.)

Table 2: Standard Sensor Specifications

Combustible

Gas (%LEL

1

)

Combustible

Gas (PPM

2

)

Oxygen

Hydrogen

Sulfide

Carbon

Monoxide

Range

0 to 100% LEL

Depends on

target gas

4

0 to 40% O

2

0 to 100 ppm

0 to 500 ppm

Alarm 1

10% LEL

5000 ppm

19.5% O

2

(decreasing)

10.0 ppm

25 ppm

Alarm 2

50% LEL

25,000 ppm

23.5% O

2

(increasing)

30.0 ppm

50 ppm

TWA Alarm

N/A

N/A

N/A

10.0 ppm

25 ppm

STEL Alarm

N/A

N/A

N/A

15.0 ppm

400 ppm

Detection
Principle

Catalytic

combustion

Catalytic

combustion

Electro-

chemical

Electro-

chemical

Electro-

chemical

Response Time
(to 90%)

15 seconds

15 seconds

20 seconds

40 seconds

55 seconds

Accuracy
(of full-scale)

± 5%

± 5%

± 5%

± 5%

± 5%

1 LEL (Lower Explosive Limit)

2 PPM (Parts Per Million)

3 Alarms settings are user adjustable. See “Updating the Alarm Point Settings” on page 36.

4 The PPM range represents the same range as 0 to 100% LEL for that gas. For example, 100% LEL for methane = 5% by

volume = 50,000 PPM. Therefore, the PPM range for methane is 0 to 50,000.