Environment

Operating Temperatures

PowerFlex 700 drives are designed to operate at 0…40 °C ambient. To operate the
drive in installations between 41…50 °C, see

Table 2

and refer to pages

42

through

44

for exceptions.

Table 2 - Acceptable Surrounding Air Temperature & Required Actions

Minimum Mounting Clearances & Heat Dissipation

The drive must be mounted with sufficient space at the top, sides, and front of the
cabinet to allow for proper heat dissipation.

Removing the Frame 7 Cover

1.

Loosen lower panel screws and pull
the bottom edge out.

2.

Tilt panel sufficiently to remove
Hinge Tabs from the upper panel.
Remove panel and set aside.

3.

Loosen upper panel screws and pull
bottom edge out slightly.

4.

Slide panel down until Locating
Tabs clear chassis. Remove panel
and set aside.

5.

Replace panels in reverse order.
Carefully align tabs and light pipes.

Enclosure Rating

Temperature Range

Drive

IP20, NEMA/UL Type 1

0…40 °C (0…104 °F)

Frames 7…10

IP00, NEMA/UL Type Open/Flange Mount

Front: IP00, NEMA/UL Type Open
Back/Heat Sink: IP54, NEMA12

0…65 °C (0…149 °F) Control Board
0…40 °C (0…104 °F) Heat Sink Entry Air

Frames 7…10

Roll In

Front: IP00, NEMA/UL Type Open
Back/Heat Sink: IP54, NEMA12

0…65 °C (0…149 °F) Control Board
0…40 °C (0…104 °F) Heat Sink Entry Air

Frames 8…9

Frame

Recommendations

7

Minimum of 152 mm (6.0 in.) at the top and bottom of the enclosure and 102 mm (4.0 in.) on the sides.
Flange Mount - Minimum of 152 mm (6.0 in.) at the back of the enclosure (flange mount surface to wall).

8…10

Minimum of 152 mm (6.0 in.) at the top of the enclosure. Additionally, allow a minimum of 102 mm (4.0 in.)
on each side OR 152 mm (6.0 in.) in the back.
Flange Mount - Minimum of 102 mm (4.0 in.) on each side.

PORT

POWER

STS

NET A
NET B

MOD

Locating Tabs
(backside of panel)

Hinge Tabs

Light Pipes