PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10

Hardware Enable Circuitry (Vector Control Only)

By default, the user can program a digital input as an Enable input. The status of
this input is interpreted by drive software. If the application requires the drive to
be disabled without software interpretation, a “dedicated” hardware enable
configuration can be utilized. This is done by removing a jumper and wiring the
enable input to “Digital In 6.”

1.

Remove HIM support plate to gain access to the Main Control Board (see
pages

8

through

11

).

2.

Locate & remove Jumper J10 on the Main Control Board (see below).

3.

Wire Enable to “Digital In 6” (see

page 51

).

4.

Verify that [Digital In6 Sel], parameter 366 is set to “1, Enable.”

Hardware Enable Jumper (J10) Location

Encoder Interface Option

Encoder Terminal Designations

No.

Description

8

+12V

(1)

DC Power

(1) Jumper selectable +5/12V is available on 20B-ENC-1 Encoder Boards.

Internal power source
250 mA.

7

+12V

(1)

DC Return (Common)

6

Encoder Z (NOT)

Pulse, marker or registration input.

(2)

(2) Z channel can be used as a pulse input while A & B are used for encoder.

5

Encoder Z

4

Encoder B (NOT)

Quadrature B input.

3

Encoder B

2

Encoder A (NOT)

Single channel or quadrature A input.

1

Encoder A

8

1