PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10

Wire Recommendations

I/O Terminal Block Specifications

Type

Wire Type(s)

Description

Min.
Insulation
Rating

Signal

(1) (2) (3)

(1) Control and signal wires must be separated from power wires by at least 0.3 meters (1 foot).

(2) If the wires are short and contained within a cabinet which has no sensitive circuits, the use of shielded wire may not be necessary,

but is always recommended.

(3) I/O terminals labeled “(–)” or “Common” are not referenced to earth ground and are designed to greatly reduce common mode

interference. Grounding these terminals can cause signal noise.

Standard Analog
I/O

Belden 8760/9460
(or equivalent)

0.750 mm

2

(18AWG), twisted pair,

100% shield with drain.

300V,
75…90 °C
(167…194 °F)

Belden 8770
(or equivalent)

0.750 mm

2

(18AWG), 3 conductor,

shielded for remote pot only.

Encoder/Pulse I/O
<30 m (100 ft.)

Combined:
Belden 9730

(4)

(4) 9730 is 3 individually shielded pairs (2 channel + power). If 3 channel is required, use 9728.

0.196 mm

2

(24AWG), individually

shielded

Encoder/Pulse I/O
30 to 152 m
(100 to 500 ft.)

Signal:
Belden 9730/9728

(4)

0.196 mm

2

(24AWG), individually

shielded

Power: Belden 8790

(5)

(5) 8790 is 1 shielded pair.

0.750 mm

2

(18AWG)

Combined:
Belden 9892

(6)

(6) 9892 is 3 individually shielded pairs (3 channel) + 1 shielded pair for power.

0.330 mm

2

(22AWG) or 0.500 mm

2

(20AWG)

Encoder/Pulse I/O
152 to 259 m
(500 to 850 ft.)

Signal:
Belden 9730/9728

(4)

0.196 mm

2

(24AWG), individually

shielded

Power: Belden 8790

(5)

0.750 mm

2

(18AWG)

Combined:
Belden 9773/9774

(7)

(7) 9773 is 3 individually shielded pairs (2 channel + power). If 3 channel is required, use 9774.

0.750 mm

2

(18AWG), individually

shielded

Digital I/O

(1)(2)(3)

Shielded

Multi-conductor shielded
cable such as Belden
8770 (or equivalent)

0.750 mm

2

(18AWG), 3 conductor,

shielded.

300V,
60 °C (140 °F)

Unshielded

Per US NEC or applicable
national or local code

Name

Description

Wire Size Range

(1)

(1) Maximum/minimum that the terminal block accepts - these are not recommendations.

Torque

Maximum

Minimum

Maximum

Recommended

I/O Terminal Block

Signal & control
connections

4.0 mm

2

(12 AWG)

0.049 mm

2

(30 AWG)

0.6 N•m
(5.3 lb•in)

0.6 N•m
(5.3 lb•in)

Encoder Terminal
Block

Encoder power & signal
connections

0.75 mm

2

(18 AWG)

0.196 mm

2

(24 AWG)

0.6 N•m
(5.3 lb•in)

0.6 N•m
(5.3 lb•in)