Jumper Settings and Locations

Fram

e

Vo

lt

ag

e

Code

Current

Ra

ti

ng

Factory Default Jumper Settings

Power Source Type

MOV

(1) (2)

7

All

All

A green/yellow wire connected to a
ground stud on the drive chassis.

Solid Ground
Connect the green/yellow MOV jumper wire to the
ground stud on the drive chassis.

Non-Solid Ground
The green/yellow MOV jumper wire must be
insulated from ground. If necessary, remove the
wire from the stud on the drive chassis. Insulate/
secure the wire to guard against unintentional
contact with the chassis or components.

8…9

All

All

A green/yellow wire connected to the PE
bus bar.

Solid Ground
Connect the green/yellow MOV jumper wire to
“PE.”

Non-Solid Ground
Remove the green/yellow MOV jumper wire from
the PE bus bar. Insulate/secure the wire to guard
against unintentional contact with the chassis or
components.

+DC

USE 75

°

COPPER WIRE ONLY

TORQUE LARGE TERMINALS TO 10 N-m (87LB-IN)

-DC

PE

PE

R-L1

T-L3

RISK OF SHOCK
REPLACE AFTER

SERVICING

!

DANGER

U-M1

V-M2

W-M3

S-L2

TB11

25 AMPERES RMS

MAXIMUM

ALLEN-BRADLEY

MADE IN U.S.A.

PE

MOV

Ground

Stud

V

W

U

R

S

T

DC-

DC+

GND

MOV

(under boards)

PE Bus

Bar