Power terminal blocks, Table 4, Refer to pag es 8 through 11 for typical locations – Rockwell Automation 20D PowerFlex 700 Installation Instructions - Frames 7…10 User Manual

Page 33

Advertising
background image

Rockwell Automation Publication 20B-IN014H-EN-P - June 2013

33

PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10

Typical Location - Phase Select Jumper

Table 4 - 380…480 Volt Single-Phase AC Input Ratings

Power Terminal Blocks

Refer to pages

8

through

11

for typical locations.

480V Single-Phase AC Input

380…400V Single-Phase AC Input

Temp.

Drive
Catalog
Number

Fr

am

e

Hp
Rating

Input
Amps

Three-Phase
Output

Drive
Catalog
Number

Fr

am

e

kW
Ratin
g

Input
Amps

Three-Phase
Output

V AC

Amps

V AC

Amps

°C

20BD292

7

125

237.4

0-460

146

20BC292

7

80

247.7

0-400

146

25

20BD325

7

125

264.3

0-460

162.5

20BC325

7

90

275.7

0-400

162.5

25

ATTENTION: National Codes and standards (NEC, VDE, BSI etc.) and local codes
outline provisions for safely installing electrical equipment. Installation must
comply with specifications regarding wire types, conductor sizes, branch circuit
protection and disconnect devices. Failure to do so can result in personal injury
and/or equipment damage.

Name

Frame

Description

Wire Size Range
see Note

(2)

(2) Maximum/minimum sizes that the terminal block accepts - these are not recommendations.

Torque

Maximum

Minimum

Maximum

Recommended

Power
Terminal Block

7

Input power, DC+,
DC–, PE, motor
connections

150.0 mm2
(300 MCM)
see Note

(3)

(3) If can be necessary to connect multiple wires in parallel to these terminals by using multiple lugs.

2.5 mm

2

(14 AWG)

2.7 N•m
(24 lb•in)

2.7 N•m
(24 lb•in)

8…10

Input power, DC+,
DC–, PE, motor
connections

300.0 mm2
(600 MCM)
see Note

(3)

2.5 mm

2

(14 AWG)

10.0 N•m
(87 lb•in)

10.0 N•m
(87 lb•in)

AUX Terminal
Block

(1)

7…10

Auxiliary Control
Voltage
PS+, PS–

(1)

(1) External control power - select drives only, see

Auxiliary Control Power Supply on page 39

for details.

4.0 mm

2

(12 AWG)

0.049 mm

2

(30 AWG)

0.6 N•m
(5.3 lb•in)

0.6 N•m
(5.3 lb•in)

Fan Terminal
Block

7

User Supplied Fan
Voltage

4.0 mm

2

(12 AWG)

0.5 mm

2

(22 AWG)

0.9 N•m
(8.0 lb•in)

0.6 N•m
(5.3 lb•in)

8…10

4.0 mm

2

(12 AWG)

0.5 mm

2

(22 AWG)

0.6 N•m
(5.3 lb•in)

0.6 N•m
(5.3 lb•in)

LINE
TYPE

SPARE 1

SPARE 2

3-PH 1-PH

JP1

JP2

JP3

1-PH 3-PH

LINE T

YPE

3

3

3

AC Input

Precharge

Board

Advertising