Rockwell Automation Publication 20B-IN014H-EN-P - June 2013

53

PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10

Input/Output

Connection Example

Required Parameter Changes

Analog Output
±10V, 0-20 mA Bipolar
+10V Unipolar (shown)

Configure with Parameter 340
Select Source Value:

Parameter 380, [Digital Out1 Sel]

Adjust Scaling:

Parameters 343/344

2-Wire Control Non-
Reversing

(1)

24V DC internal supply

(1) Important: Programming inputs for 2 wire control deactivates all HIM Start buttons unless parameter 192, [Save HIM

Ref], bit 1 [Manual Mode] = “1.” This allows the HIM to control Start and Jog.

Disable Digital Input:#1:

Parameter 361 = “0, Unused”

Set Digital Input #2:

Parameter 362 = “7, Run”

Set Direction Mode:

Parameter 190 = “0, Unipolar”

2-Wire Control
Reversing

(1)

External supply
(I/O Board dependent)

Set Digital Input:#1:

Parameter 361 = “8, Run
Forward”

Set Digital Input #2:

Parameter 362 = “9, Run
Reverse”

3-Wire Control
Internal supply

No Changes Required

3-Wire Control
External supply
(I/O Board dependent).
Requires 3-wire functions
only ([Digital In1 Sel]).
Using 2-wire selections
causes a type 2 alarm.

No Changes Required

Digital Input
PLC Output Card (Board
dependent).

No Changes Required

Digital Output
Relays (two at terminals 14-
16) shown in powered state
with drive faulted. See page

51

.

Select Source to Activate:

Parameters 380/384

Enable Input

Configure with parameter 366

For dedicated hardware Enable:
Remove Jumper J10 (see page

54

)

+

24
25
26

28

Stop-Run

25

27
28

Run Rev.

Run Fwd.

115V/

+24V

Neutral/

Common

Start

24
25
26
27
28

Stop

Start

25

27
28

Stop

115V/

+24V

Neutral/

Common

25

27
28

Control from
Prog. Controller

Neutral/

Common

10k Ohm, 2 Watt

Power Source

11
12
13
14
15
16

Fault
NOT Fault

NOT Run
Run

or

32