PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10

Drive Status Indicators & DPI Port Locations

No.

Name

Color

State

Description

➊

PWR
(Power)

Green

Steady

Illuminates when power is applied to the drive.

➋

STS
(Status)

Green

Flashing

Drive ready, but not running and no faults are present.

Steady

Drive running, no faults are present.

Yellow

Flashing, Drive Stopped

A start inhibit condition exists, the drive cannot be started.
Check parameter 214 [Start Inhibits].

Flashing, Drive Running

An intermittent type 1 alarm condition is occurring.
Check parameter 211 [Drive Alarm 1].

Steady, Drive Running

A continuous type 1 alarm condition exists.
Check parameter 211 [Drive Alarm 1].

Red

Flashing

Fault has occurred. Check [Fault x Code] or Fault Queue.

Steady

A non-resettable fault has occurred.

➌

PORT

Refer to the Communication
Adapter User Manual.

Status of DPI port internal communications (if present).

MOD

Status of communications module (when installed).

NET A

Status of network (if connected).

NET B

Status of secondary network (if connected).

➍

DPI Port 1

HIM connection.

➎

DPI Port 5

Cable connection for communications adapter.

➏

DPI Port 3 or 2

Splitter cable connected to DPI Port 2 provides additional port.

➐

DPI Port 2

Cable connection for handheld and remote options. Located
on side of chassis for Frame 7 IP20, NEMA/UL Type 1.

TB11

TE

25 AMPERES RMS

MAXIMUM

PORT

NET A
NET B

MOD

➊

➋

➌

2

1or3

➍

➐

➏

➊

➋

➌

➎

Important:
Verify metal
ground tab is
bent 90° and is
under the adapter before
tightening screw. After
tightening the screw, verify
that continuity exists
between the head of the
screw and drive ground.