Step 4: I/O Wiring

Important points to remember about I/O wiring:

Use Copper wire only. Wire gauge requirements and recommendations are
based on 75 degrees C. Do not reduce wire gauge when by using higher
temperature wire.

Wire with an insulation rating of 600V or greater is recommended.

Separate control and signal wires from power wires by at least 0.3 meters (1
foot).

10

All

All

A green/yellow wire connected to
chassis

Solid Ground
Connect the green/yellow MOV jumper wire to the
chassis.

Non-Solid Ground
Remove the green/yellow MOV jumper wire from
the chassis. Insulate/secure the wire to guard
against unintentional contact with the chassis or
components.

(1) AC input drives only. MOV’s do not exist on DC input drives.

(2) Frame 7…10 drives do not have common mode capacitors.

Fram

e

Vo

lt

ag

e

Co

de

Curr

ent

Ra

ti

n

g Factory Default Jumper Settings

Power Source Type

MOV

(1) (2)

120
IN1

120
IN2

3

4

5

6

TB10

8 AMPERES RMS

MAXIMUM

GND

RISK OF SHOCK
REPLACE AFTER

SERVICING

!

DANGER

MOV

Jumper Wire

Converter Section

IMPORTANT

I/O terminals labeled “(–)” or “Common” are not referenced to earth ground
and are designed to greatly reduce common mode interference. Grounding
these terminals can cause signal noise.

ATTENTION: Configuring an analog input for 0…20 mA operation and driving
it from a voltage source could cause component damage. Verify proper
configuration prior to applying input signals.

ATTENTION: Hazard of personal injury or equipment damage exists when
using bipolar input sources. Noise and drift in sensitive input circuits can cause
unpredictable changes in motor speed and direction. Use speed command
parameters to help reduce input source sensitivity.