Rockwell Automation Publication 20B-IN014H-EN-P - June 2013

59

PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10

Step 5: Start-Up Check List

This check list supports the Basic Start-Up menu option. See

page 64

for

information on other start-up routines.

A Human Interface Module (HIM) is required to run the Basic Start-Up
routine.

The Basic Start-Up routine can modify parameter values for Analog and
Digital I/O. Refer to Common I/O Programming Changes on

page 70

.

Prepare For Drive Start-Up

1.

Confirm that all inputs are connected to the correct terminals and are
secure.

2.

Verify that AC line power at the disconnect device is within the rated value
of the drive.

3.

Verify that control power voltage is correct.

4.

The remainder of this procedure requires that a HIM be installed.
Connect a Human Interface Module (HIM) to Drive Peripheral Interface
(DPI) Port 1 or 2. If an operator interface is not available, use remote
devices to start up the drive.

5.

Apply AC power and control voltages to the drive.

If any of the six digital inputs are configured to “Stop – CF”
(CF = Clear Fault) or “Enable,” verify that signals are present or
reconfigure [Digital Inx Sel], parameters 361…366. If an I/O option is not
installed (i.e. no I/O terminal block), verify that [Digital Inx Sel] is not
configured to “Stop – CF” or “Enable.” If this is not done, the drive will
not start. Refer to

Abbreviated Fault Listing

on

page 71

for a list of

potential digital input conflicts.

If the STS LED is not flashing green at this point, refer to

Drive Status

Indicators & DPI Port Locations

on

page 68

.

6.

When prompted, select a display language. The PowerFlex 700 Start-Up
Screen is displayed.

7.

Press the Enter key to display the Start-Up Menu.

8.

Use the Arrow keys to highlight “2. Basic”.

ATTENTION: Power must be applied to the drive to perform the following
start-up procedure. Some of the voltages present are at incoming line potential.
To avoid electric shock hazard or damage to equipment, allow only qualified
service personnel to perform the following procedure. Thoroughly read and
understand the procedure before beginning.

IMPORTANT

When power is first applied, the HIM can require approximately 5 seconds until
commands are recognized (including the Stop key). An explanation of the LED
indicators can be found on

page 68

.