Rockwell Automation Publication 20B-IN014H-EN-P - June 2013

51

PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10

I/O Terminal Designations

No.

Signal

Fa

ct

or

y

Defa

ult

Description

Re

lat

ed

Pa

ra

m

.

1

Analog In 1 (–)

(1)

(1) Important: 0…20mA operation requires a jumper at terminals 17 & 18 (or 19 & 20). Drive damage can occur if jumper is not

installed.

(3)

(3) These inputs/outputs are dependant on a number of parameters (see “Related Parameters”).

Isolated

(4)

, bipolar, differential, ±10V/4-20mA, 11 bit & sign, 88k

ohm input impedance. For 4-20mA, a jumper must be installed at
terminals 17 & 18 (or 19 & 20).

(4) Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high common mode

immunity.

320…
327

2

Analog In 1 (+)

(1)

3

Analog In 2 (–)

(1)

4

Analog In 2 (+)

(1)

5

Pot Common

–

For (+) and (–) 10V pot references.

6

Analog Out 1 (–)

(3)

Bipolar (current output is not bipolar), ±10V/4-20mA, 11 bit & sign,
voltage mode - limit current to 5 mA. Current mode - max. load
resistance is 400 ohms.

340…
347

7

Analog Out 1 (+)

8

Analog Out 2 (–)

9

Analog Out 2 (+)

10

HW PTC Input 1

–

1.8k ohm PTC, Internal 3.32k ohm pull-up resistor

238, 259

11

Digital Out 1 – N.C.

(2)

(2) Contacts in unpowered state. Any relay programmed as Fault or Alarm energizes (picks up) when power is applied to the drive and

deenergizes (drops out) when a fault or alarm exists. Relays selected for other functions energize only when that condition exists
and deenergize when condition is removed.

Fault

Max. Resistive Load:
240V AC/30V DC – 1200VA, 150W
Max. Current: 5A, Min. Load: 10mA
Max. Inductive Load:
240V AC/30V DC – 840VA, 105W
Max. Current: 3.5A, Min. Load: 10mA

380…
391

12

Digital Out 1 Common

13

Digital Out 1 – N.O.

(2)

NOT Fault

14

Digital Out 2 – N.C.

(2)

NOT Run

15

Digital Out 2/3 Com.

16

Digital Out 3 – N.O.

(2)

Run

17

Current In Jumper

(1)

–

Analog In 1

Placing a jumper across terminals 17 & 18 (or 19 & 20) configures that
analog input for current.

18

19

Current In Jumper

(1)

–

Analog In 2

20

21

–10V Pot Reference

–

2k ohm minimum load.

22

+10V Pot Reference

–

23

HW PTC Input 2

–

See above

24

+24VDC

(5)

–

Drive supplied logic input power.

(5)

(5) 150mA maximum Load. Not present on 115V versions.

25

Digital In Common

–

26

24V Common

(5)

–

Common for internal power supply.

27

Digital In 1

Stop - CF

115V AC, 50/60 Hz - Control & I/O Cat. No. option D
Opto isolated
Low State: less than 30V AC
High State: greater than 100V AC
24V DC - Control & I/O Cat. No. option C
Opto isolated
Low State: less than 5V DC
High State: greater than 20V DC
11.2 mA DC

361…
366

28

Digital In 2

Start

29

Digital In 3

Auto/Man.

30

Digital In 4

Speed Sel 1

31

Digital In 5

Speed Sel 2

32

Digital In 6/Hardware
Enable, see pg.

54

Speed Sel 3

33

Digital Out 4 – N.C.

Fault

Dedicated fault output - Not user configurable. Relay energizes (picks
up) when power is applied to the drive and deenergizes (drops out)
when a fault exists. See Terminals 11-16 for specs.

34

Digital Out 4 Common

35

Digital Out 4 – N.O.

NOT Fault

PS+

Aux. Control Power (+)

Refer to

page 39

.

PS-

Aux. Control Power (–)

Refer to

page 39

.

PE

PE Ground

PE Ground

PE

PE Ground

PE Ground