PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10

Additional Frame 10 Wiring Requirement for IP00 AC Input Drives

The Inverter and Converter sections of Frame 10 AC Input IP00, NEMA/UL
Type Open drives are shipped separately. Once installed, the following
connections are required.

1.

DC Link Choke Wiring
DC link chokes are supplied loose for customer mounting and wiring in
IP00 drives. Refer to

DC Link Chokes – Frames 8…10

below.

2.

Thermistor Wiring
Thermistor wiring is coiled loose in the Converter section for shipping.
Locate the wire (labeled “To INV”) and route through the enclosure wall.
Connect it to the mating connector above the HIM cradle.

3.

Ground the drive chassis
Refer to

page 11

for IP00 PE grounding locations.

DC Link Chokes – Frames 8…10

DC Link Chokes are supplied with Frame 8…10 AC input drives.

DC Link Choke Wiring

Refer to the diagram and page

34

for

connection information. Drive rating
information can be found on pages

42

42

.

ATTENTION: To avoid possible drive damage, ensure that the
thermistor wiring described above has been properly performed.

Frame

Type

DC Link Choke is supplied …

8…9

IP00, NEMA/UL Type Open

Mounted and wired

IP20, NEMA/UL Type 1

Mounted and wired

IP00, NEMA/UL Type Open Roll-In

Loose without cables (see wiring info below)

10

IP00, NEMA/UL Type Open

Loose without cables (see wiring info below)

IP20, NEMA/UL Type 1

Mounted and wired

Output to Inverter

Capacitor Bank

Input from

Converter

CNV+

CNV–

INV+

(1)

(2)

(4)

(3)

INV–

DC–

DC+

to Mounting Foot