Manually clearing faults – Rockwell Automation 20D PowerFlex 700 Installation Instructions - Frames 7…10 User Manual
Page 75
Advertising
Rockwell Automation Publication 20B-IN014H-EN-P - June 2013
75
PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10
Manually Clearing Faults
Step
Key(s)
1. Press Esc to acknowledge the fault. The fault information is removed so that you can use the
Human Interface Module (HIM).
2. Address the condition that caused the fault.
3. The cause must be corrected before the fault can be cleared.
4. After corrective action has been taken, clear the fault by one of these methods:
– Press Stop
– Cycle drive power
– Set parameter 240 [Fault Clear] to “1.”
– “Clear Faults” on the Human Interface Module (HIM) Diagnostic menu.
Esc