Fan circuit power supply, Frame 7 frame 8 – Rockwell Automation 20D PowerFlex 700 Installation Instructions - Frames 7…10 User Manual

Page 35

Advertising
background image

Rockwell Automation Publication 20B-IN014H-EN-P - June 2013

35

PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10

Fan Circuit Power Supply

Frame 7

Frame 8

ATTENTION: To avoid a shock hazard, ensure that all power to the drive has
been removed before connecting the fan supply.

IMPORTANT

Some drives utilize a fan transformer to power the internal fan(s). This
transformer is sized specifically for the internal fan(s) and must not be used to
power other circuitry.

Drive
Type

Enclosure

Rating
(120VAC)

No. of
Fans

Connect at …

DC
Input

IP00, NEMA/UL Type Open

250 VA

1

Power Terminal Block
Requires user supplied 120V AC. See page

34

for

location.

IP20, NEMA/UL Type 1

250 VA

1

AC
Input

IP00, NEMA/UL Type Open

250 VA

1

N/A (Connected internally)

IP20, NEMA/UL Type 1

250 VA

1

Drive
Type

Enclosure

Rating
(120VAC)

No. of
Fans

Connect at …

DC
Input

IP00, NEMA/UL Type Open

500 VA

1

TB9
Requires user supplied 120V AC. See page

9

for TB

location and page

37

for terminal designations.

IP20, NEMA/UL Type 1

500 VA

1

AC
Input

IP00, NEMA/UL Type Open

500 VA

1

TB9
A transformer
matches the input
line voltage to the
internal fan voltage. If
line voltage is
different than the
voltage class specified
on the drive
nameplate, the
transformer taps may
require changing.

IP20, NEMA/UL Type 1

500 VA

1

Input Line Voltage

480/400V AC, 50/60 Hz

F2

H3

480

400

F3

to TB9

JMP

0

115

0

F1

H2

H1

X1

XF

X2

Advertising