AC Precharge Board LED Indications

The LEDs are above the “Line Type” jumper shown on

page 33

.

Name

Color

State

Description

Power

Green

Steady

Indicates when precharge board power supply is operational

Alarm

Yellow

Flashing
[1]
[2]
[3]
[4]
[5]
[6]
[7]

Number in “[ ]” indicates flashes and associated alarm

(1)

:

Low line voltage (<90%).
Very low line voltage (<50%).
Low phase (one phase <80% of line voltage).
Frequency out of range or asymmetry (line sync failed).
Low DC bus voltage (triggers ride-through operation).
Input frequency momentarily out of range (40…65 Hz).
DC bus short circuit detection active.

(1) An alarm condition automatically resets when the condition no longer exists

Fault

Red

Flashing
[2]
[4]

Number in “[ ]” indicates flashes and associated fault

(2)

:

DC bus short (Udc <2% after 20 ms).
Line sync failed or low line (Uac <50% Unom).

(2) A fault indicates a malfunction that must be corrected and can only be reset after cycling power.