Rockwell Automation Publication 20B-IN014H-EN-P - June 2013

PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10

9.

Press the Enter key. Follow the menu by using the Enter key which steps
you through the Start-Up routine.

The Basic Start-Up routine asks simple questions and prompts you to
input required information. See also

Common I/O Programming

Changes

on

page 70

.

Information About Start-Up Motor Tests

Control schemes vary based on which Start/Jog Source is selected in Step 3.
Motor Tests.

During motor tests and tuning procedures, the drive can modify certain
parameter values for proper Start Up operation. These values are then reset to
their original values when Start Up is complete. The affected parameters are: 053,
080, 276, 278 and 361…366. If power is removed from the drive during the tests
without aborting the auto-tune procedure, these parameters cannot reset to their
original value. If this situation occurs, reset the drive to factory defaults (see

page 70

) and repeat the Start Up procedure.

Start/Jog Source

Control Source Description

Digital Inputs

Digital In 1 = Stop / Digital In 2 = Start / Digital In 3 = Jog

Local Human Interface
Module (HIM)–Port 1

Human Interface Module (HIM) connected to DPI Port 1 controls Stop / Start / Jog
Digital In 1…6 are temporarily disabled during motor tests.

Remote HIM

Human Interface Module (HIM) connected to DPI Port 2 controls Stop / Start / Jog
Digital In 1…6 are temporarily disabled during motor tests.