Rockwell Automation Publication 20B-IN014H-EN-P - June 2013

29

PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10

DC Link Choke – Frame 10

Step 3: Wire the Drive

Special Considerations

PowerFlex 700 drives are suitable for use on a circuit capable of delivering up to a
maximum of 200,000 rms symmetrical amperes.

If a system ground fault monitor (RCD) is used, only Type B (adjustable) devices
can be used to avoid nuisance tripping.

12.7 (0.50)

31.8 (1.25)

222.0

(8.74)

25.4

(1.00) Dia.

2 Places

34.9 (1.38)

57.2 (2.25)

121.8 (4.80)

9.5 (0.38) Dia.

251.0

(9.90)

220.9 (8.70)

244.6 (9.63)

Top

Front

Side

266.7 (10.50) Max

280.7

(11.05)

219.7

(8.65)

See Detail

280.7 (11.05)

248.0

(9.76)

305.0

(12.00)

247.7

(9.75)

11.8 (0.47)

12.7 (0.50)

7.9 (0.31)

4 PLACES

13.5 (0.53)

31.8 (1.25)

Detail

Dimensions are in millimeters and (inches)

ATTENTION: To guard against personal injury and/or equipment damage
caused by improper fusing or circuit breaker selection, use only the
recommended line fuses/circuit breakers specified on

page 41

.