Rockwell Automation Publication 20B-IN014H-EN-P - June 2013

57

PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10

Speed Reference Selection Chart

(1)

Auto/Manual Examples

PLC = Auto, HIM = Manual
A process is run by a PLC when in Auto mode and requires manual control from
the HIM during set-up. The Auto speed reference is issued by the PLC through a
communications module installed in the drive. Because the internal
communication is designated as Port 5, [Speed Ref A Sel] is set to “DPI Port 5”
with the drive running from the Auto source.

Attain Manual Control

Press ALT then Auto/Man on the HIM. When the HIM attains
manual control, the drive speed command comes from the HIM speed
control keys.

Release to Auto Control

Press ALT then Auto/Man on the HIM again. When the HIM releases
manual control, the drive speed command returns to the PLC.

PLC = Auto, Terminal Block = Manual
A process is run by a PLC when in Auto mode and requires manual control from
an analog potentiometer wired to the drive terminal block. The auto speed
reference is issued by the PLC through a communications module installed in the
drive. Because the internal communication is designated as Port 5, [Speed Ref A
Sel] is set to “DPI Port 5” with the drive running from the Auto source. Since the
Manual speed reference is issued by an analog input (“Analog In 1 or 2”), [TB
Man Ref Sel] is set to the same input. To switch between Auto and Manual,
[Digital In3 Sel] is set to “Auto/Manual.”

Attain Manual Control

Close the digital input.
With the input closed, the speed command comes from the pot.

Release to Auto Control

Open the digital input.
With the input open, the speed command returns to the PLC.

(1) To access Preset Speed 1, set parameter 090 or 093 to “Preset Speed 1.”

= Default

Speed Ref B Sel, Parameter 093

Preset Speed 2, Parameter 102

Preset Speed 3, Parameter 103

Preset Speed 4, Parameter 104

Preset Speed 5, Parameter 105

Preset Speed 6, Parameter 106

Preset Speed 7, Parameter 107

TB Man Ref Sel, Parameter 096

Digital Input

DPI Port Ref 1-6, See Parameter 209

DPI Command

Jog Speed, Parameter 100

Jog Command

HIM Requesting Auto/Manual

Trim

[Digital Inx Select]:
Speed Sel 3 2 1

0 0 1

0 1 1

0 1 0

1 0 0
1 0 1

1 1 0
1 1 1

Auto

Man

Drive Ref Rslt

Commanded

Frequency

Min/Max Speed

Acc/Dec Ramp

and

S Curve

Pure Reference

Post Ramp

to follower drive for
Frequency Reference

to follower drive for
Frequency Reference

Auto Speed Ref Options

Manual Speed Ref Options

Slip Compensation

1 "Slip Comp"

None

0 "Open Loop"

PI Output

2 "Process Pi"

Speed Adders

[Speed Mode]:

PI Exclusive Mode
[PI Configuration]:
Bit 0, Excl Mode = 0

Output Frequency

Mod Functions

(Skip, Clamp,

Direction, etc.)

Speed Ref A Sel, Parameter 090

0 0 0