Rockwell Automation Publication 20B-IN014H-EN-P - June 2013

PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10

Table 7 - Abbreviated Alarm Listing

Alarm

No

.

Ty

pe

(1)

(1) See the User Manual for a description of alarm types.

Description

Dig In
ConflictA

17

Digital input functions are in conflict. Combinations marked with a “ ” will cause an alarm.

Dig In
ConflictB

18

A digital Start input has been configured without a Stop input or other functions are in conflict.
Combinations that conflict are marked with a “ ” and will cause an alarm.

Dig In
ConflictC

19

More than one physical input has been configured to the same input function. Multiple
configurations are not allowed for the following input functions.
Forward/Reverse

Run Reverse

Bus Regulation Mode B

Speed Select 1

Jog Forward

Acc2 / Dec2

Speed Select 2

Jog Reverse

Accel 2

Speed Select 3

Run

Decel 2

Run Forward

Stop Mode B

TB Man
Ref Cflct

30

Occurs when:
“Auto/Manual” is selected (default) for [Digital In3 Sel], parameter 363 and
[TB Man Ref Sel], parameter 96 has been reprogrammed.
No other use for the selected analog input can be programmed.
Example: If [TB Man Ref Sel] is reprogrammed to “Analog In 2,” all of the factory default uses for
“Analog In 2” must be reprogrammed (such as parameters 90, 117, 128 and 179). Refer to the
Auto/Manual Examples section of the PowerFlex 700 User Manual.
To correct:
Verify/reprogram the parameters that reference an analog input or
Reprogram [Digital In3] to another function or “Unused.”

Acc2/Dec2

Accel 2

Decel 2

Jog 1/2

Jog Fwd

Jog Rev

Fwd/Rev

Acc2/Dec2

Accel 2

Decel 2

Jog 1/2

Jog Fwd

Jog Rev

Fwd/Rev

Start

Stop-CF

Run

Run Fwd

Run Rev

Jog 1/2

Jog Fwd

Jog Rev

Fwd/Rev

Start

Stop-CF

Run

Run Fwd

Run Rev

Jog 1/2

Jog Fwd

Jog Rev

Fwd/Rev