Frame 10 – Rockwell Automation 20D PowerFlex 700 Installation Instructions - Frames 7…10 User Manual

Page 37

Advertising
background image

Rockwell Automation Publication 20B-IN014H-EN-P - June 2013

37

PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10

Frame 10

Fan/Blower Terminal Blocks - Frames 8…10

Fan Transformer Specifications/Fusing

Three-Phase Blower Fusing

Drive
Type

Enclosure

Rating
(120VAC)

No. of
Fans

Connect at …

DC
Input

IP00, NEMA/UL Type Open

1000 VA

2

TB9 & 10
Requires user supplied 120V AC. See page

11

for TB

locations and page

37

for terminal designations.

IP20, NEMA/UL Type 1

1000 VA

2

AC
Input

IP00, NEMA/UL Type Open

1000 VA

3

TB9, 10 & 12
Requires user supplied 120V AC. See page

11

for TB

locations and page

37

for terminal designations.

IP20, NEMA/UL Type 1

1000 VA

3

TB9, 10 & 12
A transformer (see
page

11

) matches the

input line voltage to
the internal fan
voltage. If line voltage
is different than the
voltage class specified
on the drive
nameplate, the
transformer taps may
require changing.

Frame

Rating

Recommended Fuses

Primary (Quantity 2)

Secondary (Quantity 1)

8 & 9

500 VA

2.8A, 600V AC, KLDR/ATQR Type

6.25A, 250V AC, Time Delay

10

1000 VA

6A, 600V AC, KLDR/ATQR Type

9A, 250V AC, Time Delay

Frame

Recommended Fuses (Quantity 3)

9

5A, 600V AC, Time Delay

Input Line Voltage

480/400V AC, 50/60 Hz

F2

H3

480

400

F3

to TB9

JMP

0

115

0

F1

H2

H1

X1

XF

X2

120V

120V

N

120V

AC Input

N

PE

PE

7

Line

Neutral

To Fan(s)

Ground

NC

R

T

S

Frame 10, AC Input, IP20 Only

120V

120V

N

120V

AC Input

N

PE

PE

7

Line

Neutral

To Fan(s)

Ground

NC

TB9, TB10

TB12

Frame 9 Only

Blower TB

Frames 8…10