Rockwell Automation 1403-DM_LM_MM Powermonitor II Instruction Sheet User Manual
Page 17
Advertising
![background image](/manuals/578470/17/background.png)
Installation
2-5
1403-IN001A-US-P
Figure 2.3 Single Phase with PTs Wiring Diagram
V1
V2
V3
N
Fiber
Rx
Fiber
Tx
I1+
I2+
I3+
I4+
S1
S2
S3
S4
Scom
L/+
R14
R11
R12
R24
R21
R22
Acom
Ain
N
L2
L1
Voltage Mode = Single Phase
Voltage
Inputs
Status
Inputs
Display
Module Powermonitor II
Master Module
Power
GRD
N/-
Fuse
Fuse
Customer Supplied CT Shorting
Switch or Test Block
I1-
I2-
I3-
I4-
Current
Inputs
Analog
Input
Relay
Output
Customer
Chassis
Ground
Load
Note:
•
Careful attention must be paid to correct
phasing and polarity for proper operation.
•
All ground wires should be taken individually
to Customer Chanssis Ground for a single
point of grounding.