Rockwell Automation 1403-DM_LM_MM Powermonitor II Instruction Sheet User Manual

Page 25

Advertising
background image

Installation

2-13

1403-IN001A-US-P

Figure 2.11 3-phase 3-wire Grounded L2(B) Phase Open
Delta Direct Connect with Three CTs Wiring Diagram

V1

V2

V3

N

Fiber

Rx

Fiber

Tx

I1+

I2+

I3+

I4+

S1

S2

S3

S4

Scom

L/+

R14

R11

R12

R24

R21

R22

Acom

Ain

LINE

L1

L3

Voltage
Inputs

Status
Inputs

Power

N/-

GRD

Display
Module
Fiber

Powermonitor II
Master Module

Current
Inputs

Analog
Input

Relay
Output

I1-

I2-

I3-

I4-

Fuse

Fuse

Customer Supplied CT Shorting
Switch or Test Block

Customer
Chassis
Ground

Load

L1

L2

L3

Line-to-Line Voltage must not exceed 347V
(otherwise, step down transformers are
required).

Distribution
Ground

Note:

Careful attention must be paid to correct phasing and polarity for
proper operation.

All ground wires should be taken individually to Customer
Chassis Ground for a single point of grounding.

The Two CT wiring diagrams in Figure 2.10 may be used for any
of the delta or open delta wiring or voltage modes shown.
Whether there are two or three CTs in a circuit does NOT affect
the voltage wiring or mode selection.

Voltage Mode = Open Delta