General Operation

General Functionality

The Display Module acts as a simple terminal that
allows a user to easily view metering parameters or
change configuration items. This is accomplished by
using three modes of operation: Display mode,
Program mode, and Edit mode.

Display mode allows any user to view any of the
measured parameters that the Powermonitor II
provides including metering information, harmonic
analysis (1403-MM only), and logging information.
The user also has the option of selecting default
screens which are displayed at power-up or after 30
minutes of non-activity.

Program mode allows a privileged user to issue
commands or select a parameter to modify. Program
mode provides a basic security system where each

Powermonitor II is password protected, and only one
entity can modify a Powermonitor II; an entity
includes one of the three possible Display Modules
or the Smart Communication Card. When a user is in
Program Mode, a flashing “P” is displayed at the
bottom right-hand corner of the Display Module.

Edit mode allows the privileged user to modify the
selected parameters. When a user is in Edit mode, the
parameter being modified flashes, and the flashing
“P” remains solid.

Key Functions

The Display Module has four keys located on its
front bezel: an Escape key, Up Arrow key, Down
Arrow key, and Enter key. These keys maintain their
same functionality for all of the Display Module’s
modes making the Display Module easy to use. The
functionality of the four keys is shown in Figure 4.1.

Figure 4.1 Display Module Key Functionality

Escape Key

Up Arrow Key

Down Arrow Key

Enter Key

Display Mode

Returns to parent menu.

Steps back to the previous
parameter/menu in the list.

Steps forward to the next
parameter/menu in the list.

Steps into a sub-menu or
sets as default screen.

Program Mode

Returns to parent menu.

Steps back to the previous
parameter/menu in the list.

Steps forward to the next
parameter/menu in the list.

Steps into a sub-menu or
selects the parameter to be
modified and changes to
Edit mode.

Edit Mode

Cancels changes to the
parameter, restores the
existing value, and returns
to Program mode.

Increments the parameter/
menu value.

Decrements the parameter
value.

Saves the parameter
change to the Master
Module and returns to
Program mode.