Rockwell Automation 1403-DM_LM_MM Powermonitor II Instruction Sheet User Manual

Page 54

Advertising
background image

4-18

General Operation

1403-IN001A-US-P

Under Forward Setpoint

An under forward setpoint is the same as an over
forward setpoint, except the “Setpoint High Limit”
and the “Setpoint Low Limit” are reversed.

When the magnitude of the parameter being
monitored falls below the “Setpoint Low Limit” in
the positive direction (and stays below the limit) for a
period of time greater than the “Setpoint Action

Delay,” the setpoint becomes active. An under
forward setpoint becomes inactive when the
magnitude of the parameter being monitored exceeds
the “Setpoint High Limit” (and stays over the limit)
for a period of time greater than the “Setpoint
Release Delay.”

Figure 4.6 Under Forward

Setpoint Activated

Setpoint Deactivated

Parameter
Value

Setpoint
Low Limit

Setpoint
High Limit

Setpoint Action Delay

Setpoint

Release Delay

<

Setpoint

Release Delay

Time (s)