General Operation

4-25

1403-IN001A-US-P

Table 4.13 Snapshot Log Parameters for the Voltage and Current Block

Parameter

Description

Range

Default

Phase 1 L-N Voltage

RMS line to neutral voltage of phase 1.

0 to 999.9x10

22

Volts

Phase 2 L-N Voltage

RMS line to neutral voltage of phase 2.

0 to 999.9x10

22

Volts

Phase 3 L-N Voltage

RMS line to neutral voltage of phase 3.

0 to 999.9x10

22

Volts

3-Phase Average L-N Voltage

Average RMS voltage of phase 1, 2, and 3.

0 to 999.9x10

22

Volts

Phase 1 L-L Voltage

RMS line to line voltage between phase 1 and 2.

0 to 999.9x10

22

Volts

Phase 2 L-L Voltage

RMS line to line voltage between phase 2 and 3.

0 to 999.9x10

22

Volts

Phase 3 L-L Voltage

RMS line to line voltage between phase 3 and 1.

0 to 999.9x10

22

Volts

3-Phase L-L Voltage

Average RMS line to line voltage between phase 1, 2, and
3.

0 to 999.9x10

22

Volts

Auxiliary Voltage

AC or DC auxiliary voltage input RMS voltage.

0 to 999.9x10

22

Volts

Phase 1 Current

RMS current of phase 1.

0 to 999.9x10

22

Amps

Phase 1 Current

RMS current of phase 2.

0 to 999.9x10

22

Amps

Phase 1 Current

RMS current of phase 3.

0 to 999.9x10

22

Amps

3-Phase Average Current

Average RMS current of phase 1, 2, and 3.

0 to 999.9x10

22

Amps

Phase 4 (Neutral) Current

RMS current of phase 4, also known as neutral current.

0 to 999.9x10

22

Amps

Frequency

The frequency of the voltage.

0 to 132

Hertz

Phase Rotation

The phase rotation of a 3-phase system

0 = None
1 = ABC
2 = ACB

N/A

Voltage Positive Sequence

Magnitude of positive sequence voltage in a 3-phase
system.

0 to 999.9x10

22

Volts

Voltage Negative Sequence

Magnitude of negative sequence voltage in a 3-phase
system.

0 to 999.9x10

22

Volts

Current Positive Sequence

Magnitude of positive sequence current in a 3-phase
system.

0 to 999.9x10

22

Amps

Current Negative Sequence

Magnitude of negative sequence current in a 3-phase
system.

0 to 999.9x10

22

Amps

Voltage Unbalance

The ratio between the negative and positive sequence
voltage in a 3-phase system.

0 to 100

Percent

Current Unbalance

The ratio between the negative and positive sequence
current in a 3-phase system.

0 to 100

Percent