Technical Specifications
C-3
1403-IN001A-US-P
General Input, Output, and Environmental
Ratings
Input and Output Ratings
Control Relay
Relay Life
General Specifications
Fiber Optic Cable Assembly Specifications
Control Power 1403-xMxxA
120V/240V AC 50/60 Hz or
125V/250V DC
(0.2 Amp maximum loading)
1403-xMxxB
24V AC 50/60 Hz or
24V/48V DC
(1 Amp maximum loading)
1403-DMA
120V/240V AC 50/60 Hz or
125V/250V DC
(0.05 Amp maximum loading)
1403-DMB
12V/24V AC 50/60 Hz or
12V/24V/48V DC
(0.15 Amp maximum loading)
Voltage Inputs Nominal Full Scale Input: 120V to 347V L-N
(208V to 600V L-L)
Input Impedance: 1 Meg-Ohm minimum
Current Inputs Nominal Full Scale Input:
0 to 1 Amp (1403-xM01x)
0 to 5 Amps (1403-xM05x)
Overload Withstand:
15 Amps Continuous,
300 Amps for one second
Burden: 0.05 VA
Impedance: 0.002 Ohms
Status Inputs
Contact Closure (Internal 24V DC)
Analog Input
Nominal Input: 1.0V AC/
±
1.4V DC
Overload Withstand: 120V for one minute
Rating
50/60 Hz AC rms
DC
Maximum Resistive
Load Switching
10A at 250V
(2500VA)
10A at 30V and
0.25A at 250V
Minimum Load
Switching
10mA at 24V
10mA at 24V
UL 508, CSA 22.2,
IEC Rating Class
B300
Q300
Maximum Make
Values (Inductive
Load)
30A at 120V
15A at 240V
(3600VA)
0.55A at 125V
0.27A at 250V
(69VA)
Maximum Break
Values (Inductive
Load)
3A at 120V
1.5A at 240V
(360VA)
0.55A at 125V
0.27A at 250V
(69VA)
Maximum Motor Load
Switching
1/3 HP at 125V
1/2 HP at 250V
Parameter
Number of Operations
Mechanical
5 X 10
6
Electrical
1 X 10
5
Dielectric
Withstand
Control Power
1600 Volts (Cat. No.
1403-MMxxA, -DMA)
500 Volts (Cat. No. 1403-
MMxxB, -DMB)
Voltage Inputs
2200 Volts
Current Inputs
4160 Volts
Status Inputs
1000 Volts
Control Relays
1600 Volts
Terminal Block
(+75
°
C Cu
wire only)
1403-xM Voltage
and Current
Terminals
10 AWG (6 mm
2
) max.,
16 lb-in (1.81 Nm) Torque
1403-xM Power,
Status, Analog,
Relay, and Ground
Terminals
12 AWG (4 mm
2
) max.,
(8 lb-in (0.90 Nm) Torque
1403-NSC
Terminals
14 AWG (2.5 mm
2
)
max.,5 lb-in (0.56 Nm)
Torque
1403-DM Terminals 14 AWG (2.5 mm
2
)
max.,5 lb-in (0.56 Nm)
Torque
Operating
Temperature
-40
°
C to +60
°
C (-40
°
F to +140
°
F)
Cat. No. 1403-MM, -NSC
-20
°
C to +60
°
C (-4
°
F to +140
°
F)
Cat. No. 1403-DM
Storage
Temperature
-40
°
C to +85
°
C (-40
°
F to +185
°
F)
Humidity
5% to 95%, Non-condensing
Vibration
10 to 500 Hz: 1G Operational (
±
0.006 in.) and
2.5G Non-operational (
±
0.015 in.)
Shock
1/2 Sine Pulse, 11 ms duration: 15G
Operational and 30G Non-operational
Parameter
Minimum
Maximum
Cable Length:
Distance
between two
adjacent
devices
25 cm (approx. 10 in.) shortest
Allen-Bradley standard
500 m
(1650 ft.)
Minimum
inside bend
radius
25.4mm (1 in.) Any bends with a
shorter inside radius can
permanently damage the fiber
optic cable. Signal attentuation
increases with decreased inside
bend radii.
N/A