4-20

General Operation

1403-IN001A-US-P

Table 4.8 Setpoint Configuration

Parameter Name

Parameter Description

Range

Default

Setpoint Number

The number of the setpoint being
configured.

1 - 20

N/A

Setpoint Type

The parameter value to be evaluated by the
setpoint.

0 - 54 (see details in Table 4.I)

0

Setpoint Evaluation Condition

The operator used to evaluate the parameter
value.

0 = Over forward (+)
1 = Over reverse (-)
2 = Under forward (+)
3 = Under reverse (-)
4 = Equal (=)
5 = Not equal (<>)

0

Setpoint High Limit

The value being used as a reference to
activate the setpoint for over comparisons,
or to deactivate the setpoint for under
comparisons.
Note: This parameter is non-numeric when
viewed via the Display Module, and the
Setpoint Type is Phase Rotation, Status
input, or IEEE 519 status.

0 - 1,000,000

0

Setpoint Low Limit

The value being used as a reference to
deactivate the setpoint for over
comparisons, or to activate the setpoint for
under comparisons.
Note: This parameter is non-numeric when
viewed via the Display Module, and the
Setpoint Type is Phase Rotation, Status
input, or IEEE 519 status.

0 - 1,000,000

0

Setpoint Action Delay

The minimum time in seconds that the
setpoint limit must be exceeded
continuously before the setpoint will trigger.
Note: There could be some additional
delay due to the selected update rate of
metering or harmonic data.

0 - 9999

0

Setpoint Release Delay

The minimum time in seconds that the
setpoint limit must not be exceeded
continuously before the setpoint will release.
Note: There could be some additional
delay due to the selected update rate of
metering or harmonic data.

0 - 9999

0

Setpoint Action Type

The action that will occur when the setpoint
is triggered.

0 - 20 (see details in Table 4.J)

0