4-26

General Operation

1403-IN001A-US-P

Table 4.14 Snapshot Log Parameters for the Power Block

Parameter

Description

Range

Default

Phase 1 Power

Power of phase 1 signed to show direction.

0 to 999.9x10

22

Watts

Phase 2 Power

Power of phase 2 signed to show direction.

0 to 999.9x10

22

Watts

Phase 3 Power

Power of phase 3 signed to show direction.

0 to 999.9x10

22

Watts

3-Phase Total Power

Total power of phase 1, 2, and 3 signed to show direction.

0 to 999.9x10

22

Watts

Phase 1 Reactive Power

Reactive power of phase 1 signed to show direction.

0 to 999.9x10

22

Vars

Phase 2 Reactive Power

Reactive power of phase 2 signed to show direction.

0 to 999.9x10

22

Vars

Phase 3 Reactive Power

Reactive power of phase 3 signed to show direction.

0 to 999.9x10

22

Vars

3-Phase Total Reactive Power

Total reactive power of phases 1 to 3 signed to show direction. 0 to 999.9x10

22

Vars

Phase 1 Apparent Power

Apparent power of phase 1.

0 to 999.9x10

22

VA

Phase 2 Apparent Power

Apparent power of phase 2.

0 to 999.9x10

22

VA

Phase 3 Apparent Power

Apparent power of phase 3.

0 to 999.9x10

22

VA

3-Phase Total Apparent Power

Total apparent power of phase 1, 2, and 3.

0 to 999.9x10

22

VA

Phase 1 True Power Factor

The ratio between the power and apparent power for phase 1;
this value is signed to show lead (+) or lag (-).

-100 to 100

Percent

Phase 2 True Power Factor

The ratio between the power and apparent power for phase 2;
this value is signed to show lead (+) or lag (-).

-100 to 100

Percent

Phase 3 True Power Factor

The ratio between the power and apparent power for phase 3;
this value is signed to show lead (+) or lag (-).

-100 to 100

Percent

Total True Power Factor

The ratio between the power and apparent power for phase 1,
2, and 3; this value is signed to show lead (+) or lag (-).

-100 to 100

Percent

Phase 1 Distortion Power Factor

The ratio between the magnitude of the fundamental and the
sum of the magnitudes for all of the current harmonics for
phase 1.

(1)

0 to 100

Percent

Phase 2 Distortion Power Factor

The ratio between the magnitude of the fundamental and the
sum of the magnitudes for all of the current harmonics for
phase 2.

1

0 to 100

Percent

Phase 3 Distortion Power Factor

The ratio between the magnitude of the fundamental and the
sum of the magnitudes for all of the current harmonics for
phase 3.

1

0 to 100

Percent

Total Distortion Power Factor

The ratio between the magnitude of the fundamental and the
sum of the magnitudes for all of the current harmonics for
phase 1, 2, and 3.

1

0 to 100

Percent

Phase 1 Displacement Power
Factor

The cosine of the difference between the phase angle of the
fundamental voltage and current for phase 1; this value is
signed to show lead (+) or lag (-).

1

-100 to 100

Percent

Phase 2 Displacement Power
Factor

The cosine of the difference between the phase angle of the
fundamental voltage and current for phase 2; this value is
signed to show lead (+) or lag (-).

1

-100 to 100

Percent

Phase 3 Displacement Power
Factor

The cosine of the difference between the phase angle of the
fundamental voltage and current for phase 3; this value is
signed to show lead (+) or lag (-).

1

-100 to 100

Percent

Total Displacement Power Factor

The cosine of the difference between the phase angle of the
fundamental voltage and current for phase 1, 2, and 3; this
value is signed to show lead (+) or lag (-).

1

-100 to 100

Percent

(1) This value has the same update rate as the harmonic analysis.