Rockwell Automation 1403-DM_LM_MM Powermonitor II Instruction Sheet User Manual

Page 43

Advertising
background image

General Operation

4-7

1403-IN001A-US-P

Snapshot Buffer Type

The buffer type used by the snapshot log. Fill and Stop
stops filling the buffer when it is full or until the buffer is
reset. Circular continuously fills the buffer and overwrites
old data when the buffer is full.

0 = Fill and Stop
1 = Circular

1 = Circular

Log Status Inputs

Enables logging to the event log any activity of the 4 status
inputs.

0 = No
1 = Yes

0 = No

Log Min/Max Values

Enables logging to the Min/Max log the minimum and
maximum of specific parameters. By enabling this
function, real time metering update rates increase by 10
msec.

0 = No
1 = Yes

1 = Yes

Date Format

The format of the date that is displayed on the Display
Module.

MM/DD/YYYY
DD/MM/YYYY

MM/DD/
YYYY

Date: Year

The year of the present date.

1998 to 2097

Present
Year

Date: Month

The month of the present date.

1 to 12

Present
Month

Date: Day

The day of the present date.

0 to 31

Present Day

Time: Hour

The hour of the present time.

0 to 23

Present
Hour

Time: Minute

The minute of the present time.

0 to 59

Present
Minute

Time: Second

The second of the present time.

0 to 59

Present
Second

Time: Hundredth Second The hundredth second of the present time.

0 to 99

Present
Hundredth
Second

Max Isc

1

The maximum short circuit current which is a parameter
necessary for calculating compliance with IEEE-519.

0 to 10,000,000

0

Max Demand Load
Current

1

The maximum demand load current which is a parameter
necessary for calculating compliance with IEEE-519.

0 to 10,000,000

0

Phase Label: 1

Defines what symbol is used to designate input phase 1.

‘(space)‘to ‘z’

‘A’

Phase Label: 2

Defines what symbol is used to designate input phase 2.

‘(space)‘to ‘z’

‘B’

Phase Label: 3

Defines what symbol is used to designate input phase 3.

‘(space)‘to ‘z’

‘C’

Vaux Label: 1

Defines what symbol is used for the first of eight
characters describing Vaux.

‘(space)‘to ‘z’

‘A’

Vaux Label: 2

Defines what symbol is used for the second of eight
characters describing Vaux.

‘(space)‘to ‘z’

‘U’

Vaux Label: 3

Defines what symbol is used for the third of eight
characters describing Vaux.

‘(space)‘to ‘z’

‘X’

Vaux Label: 4

Defines what symbol is used for the fourth of eight
characters describing Vaux.

‘(space)‘to ‘z’

‘(space) ‘

Vaux Label: 5

Defines what symbol is used for the fifth of eight
characters describing Vaux.

‘(space)‘to ‘z’

‘(space) ‘

Vaux Label: 6

Defines what symbol is used for the sixth of eight
characters describing Vaux.

‘(space)‘to ‘z’

‘(space) ‘

Vaux Label: 7

Defines what symbol is used for the seventh of eight
characters describing Vaux.

‘(space)‘to ‘z’

‘V’

Vaux Label: 8

Defines what symbol is used for the eighth of eight
characters describing Vaux.

‘(space)‘to ‘z’

‘(space) ‘

Table 4.1 General Configuration

Parameter

Description

Range

Default

User

Setting

Advertising