General Operation

4-21

1403-IN001A-US-P

Table 4.9 Setpoint Type

Setpoint
Type

Description

0

Not used (inactive)

1

Voltage (any 1 of three phases, L-N in Single
Phase/Wye Modes, L-L in Delta/Open-Delta
Modes)

2

Current (any 1 of three phases)

3

Voltage unbalance

4

Current unbalance

5

Vaux voltage

6

Neutral (I4) current

7

Total kW

8

Total kVAR

9

Total kVA

10

Total true power factor

11

Total displacement power factor

12

Total distortion power factor

13

KW demand

14

KVAR demand

15

KVA demand

16

Current demand

17

Type 1 predictive demand A

18

Type 1 predictive demand W

19

Type 1 predictive demand VAR

20

Type 1 predictive demand VA

21

Type 2 predictive demand A

22

Type 2 predictive demand W

23

Type 2 predictive demand VAR

24

Type 2 predictive demand VA

25

Type 3 predictive demand A

26

Type 3 predictive demand W

27

Type 3 predictive demand VAR

28

Type 3 predictive demand VA

29

Frequency

30

Phase rotation

31

(1)

K-factor: voltage (any 1 of three phases)

32

(1)

K-factor: current (any 1 of three phases)

33

(1)

K-factor: neutral current

34

(1)

Crest factor: voltage (any 1 of three phases)

35

(1)

Crest factor: current (any 1 of three phases)

36

(1)

Crest factor: neutral current

37

(1)

TIF: voltage (any 1 of three phases)

38

(1)

TIF: current (any 1 of three phases)

39

(1)

TIF: neutral current

40

IEEE THD: voltage (any 1 of three phases)

41

IEEE THD: current (any 1 of three phases)

42

IEEE THD: neutral current

43

IEC THD: voltage (any 1 of three phases)

44

IEC THD: current (any 1 of three phases)

45

IEC THD: neutral current

46

(1)

IEEE519: voltage (any 1 of three phases)

47

(1)

IEEE519: current (any 1 of three phases)

48

(1)

IEEE519: neutral current

49

Status input #1

50

Status input #2

51

Status input #3

52

Status input #4

53

Any status input

54

Battery usage timer

(1) Available on 1403-MM only.

Table 4.10 Setpoint Action Type

Setpoint Action
Type

Description

0

No action

1

Energize relay1 and set alarm flag1

2

Energize relay2 and set alarm flag2

3

Set alarm flag3

4

Set alarm flag4

5

Set alarm flag5

6

Set alarm flag6

7

Set alarm flag7

8

Set alarm flag8

9

Set alarm flag9

10

Set alarm flag10

11

Set alarm flag11

12

Set alarm flag12

13

Set alarm flag13

14

Set alarm flag14

15

Set alarm flag15

16

Set alarm flag16

17

1

Initiate oscillograph

18

Perform snapshot

19

Clear kWh power counter

20

Clear kVARh power counter

Table 4.9 Setpoint Type

Setpoint
Type

Description